Study on Short Circuit-current Distribution Characteristics of Overhead Transmission Line-GIL Hybrid Transmission System
weather and external environment due to the adoption of pipe sealing insulation and transmission
therefore
the power transmission by the use of overhead line-GIL hybrid system will become more and more common. In case of short circuit fault of the hybrid system
its current distribution will be different from that of the normal transmission line. For clarifying short circuit current shunt of the hybrid system
the overhead line-GIL hybrid transmission system model is set up firstly in this paper. The current enhancement factor of three-phase conductor in GIL is between 1.01 and 2.08 through setting earth short circuit fault at the side of power transmission conductor by way of closing operation of the switch. The current enhancement factor in the case of threephase earthing short circuit fault is maximum. In case of setting the earthing short circuit fault of internal conductor of GIL
the current enhancement factor of three-phase conductor in the GIL is between 1.05 and 21.58. Similarly
the current enhancement factor in the case of three-phase earthing short circuit fault is maximum
which has provided technical support for the safe design of the GIL transmission system.