Research and Design on 12 kV Outgoing Switchgear Considering Live Maintenance Function
a kind of design scheme for the live maintenance of 12 kV outgoing switchgear is proposed in order to reduce the power off time and improve power supply reliability.Firstly
the primary wiring of the switchgear is optimized and the method of installing a double-action switch in the middle part of the standby switchgear is proposed to achieve the purpose of live maintenance.For assessing operation reliability of the switchgear at rated voltage
a 3D temperature field and electric field model of the switchgear are set up and the simulation calculation of
the temperature field and electric field is performed.A 3D transient electric field model is set up to analyze the influence of overvoltage on switchgear insulation at switching condition of the double-action switch and the lightning impulse condition respectively.The research results show that the maximum field strength of the main switchgear and the standby switchgear is 7.82×10
4
V/m and 9.47×10
4
V/m respectively
is less than the air breakdown field strength and the dielectric condition is good.The maximum temperature rise of the main switchgear and the standby switchgear is 50.7 K and 42.8 K and meets related standard requirements.The peak of overvoltage generated during the switching process of the main switchgear and standby switchgear is 16.6 kV.At this time
the maximum electric field strength of the switchgear is 4.35×10
5
V/m
which shows good dielectric performance.The maximum field strength in the main switchgear and standby switchgear at lightning impulse condition is 1.415×10
7
V/m and 5.093×10
6
V/m respectively.At this time
the installation of the lightning arrester cannot be omitted.
Research on Insulation Performance of a New CF3OCF=CF2 Alternative Gas to SF6
Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
Design and Optimization of Insulation Structure for Embedded Pole Used in Dry Air Insulation Switchgear Cabinet
Research on the Influence of Temperature and Humidity on the Physical Signal of Partial Discharge of Switchgear
RESEARCH ON THE CHARACTERISTICS OF ULTRASONIC SIGNALS OF PARTIAL DISCHARGE IN 12V SWITCHGEAR CABINET
Related Author
TANG Nian
SUN Dongwei
YAO Yuyang
LYU Jian
ZENG Jijun
ZHAO Bo
MA Yiding
GAO Wenqiang
Related Institution
State Key Lab of Electrical Insulation & Power Equipment, Xi’an Jiaotong University
Electric Power Research Institute of Guangdong Power Grid Co., Ltd.
Xi’an Modern Chemistry Research Institute
Department of Electrical and Computer Engineering University of Connecticut
Power Research Institute of State Grid Beijing Electric Power Co., Ltd.