LI Liangshu, WAN Kanghong, WANG Qiongyuan, et al. Study on Sensitivity Characteristic of Decomposed Gas of MoS2 Sensor with Insulating Medium Feature[J]. High voltageapparatus, 2021, 57(10): 36-43.
DOI:
LI Liangshu, WAN Kanghong, WANG Qiongyuan, et al. Study on Sensitivity Characteristic of Decomposed Gas of MoS2 Sensor with Insulating Medium Feature[J]. High voltageapparatus, 2021, 57(10): 36-43. DOI: 10.13296/j.1001-1609.hva.2021.10.005.
Study on Sensitivity Characteristic of Decomposed Gas of MoS2 Sensor with Insulating Medium Feature
Under the influence of discharge and overheating faults
the electrical insulating medium(SF
6
insulating oil
etc.)can decompose a series of characteristic gases.The operation condition of electrical equipment
can be assessed through compositional analysis of gas.In this paper
the layered molybdenum disulfide(MoS
2
)based on hydrothermal process is synthesized and filled in the gas sensor.The sensitive features of such six kinds of insulation medium decomposed gases as sulfuretted hydrogen(H
2
S)
sulfur dioxide(SO
2
)
carbon oxide(CO)
methane(CH
4
)
ethyne(C
2
H
2
)and hydrogen(H
2
)is analyzed.Compared to three commercial sensors with serious cross-sensitivity
MoS
2
sensor shows specific selectivity toward H
2
S.For insulating oil decomposition gases(CO
C
2
H
2
H
2
CH
4
)
MoS
2
sensor is only sensitive to CO.Furthermore
MoS
2
sensor also has outstanding performance in detecting the repletion of H
2
S and CO.During the five cycles of testing the fluctuation range of response value does not exceed 7.2%and 5.95%respectively.The result of concentration test also indicates that
in case of H
2
S and CO below 50μL/L
the linearity of MoS
2
sensor is good (9.26%and 0.62%).In addition
MoS
2
sensor shows a synergistic adsorption towards H
2
S and CO.With the increase of H
2
S concentration (10
30
50μL/L)
the influence of CO concentricity on the response values is less (6.74%
4.94%
3.47%).Thus
the layered MoS
2
has a broad application prospect in the detection of insulating medium characteristic decomposition gas.