Test and Calculation of Short-circuit Arc Explosion Wave Energy of 220 kV High Voltage Cable Joint
In case of arc fault in a high-voltage cable joint
the explosion shock wave generated by the expansion of the arc channel is the direct cause of the secondary fault. Studying the short-circuit arc explosion wave energy of the joint is essential for the structural design and explosion-proof performance inspection of the high-voltage cable joint protection device. In this paper
the 50 kA/200 ms high-current artificial short-circuit arcing test is designed and implemented and the explosion shock wave overpressure value released from the energy discharge hole of 220 kV highvoltage cable joint protection device is actually measured. The simulation model of the thermal-flow field short-circuit arc explosion of the cable joint and the protection device is set upand the shock wave overpressure released from the leak hole of energy is calculated. The explosion wave energy of short circuit arc of 220 kV cable joint is obtained by comparing the actually measured over pressure of shock wave in the artificial short circuit arcing test at the same condition. The obtained result can provide theoretical evidence for the design and test of 220 kV high voltage cable joint protection device.