JIA Yongyong, ZHU Mengzhou, YANG Jinggang, et al. High Reliability Analysis of Grounding Fault Signal of 12 kV Primary and Secondary Fusion Switchgear[J]. High voltageapparatus, 2021, 57(10): 158-166+175.
DOI:
JIA Yongyong, ZHU Mengzhou, YANG Jinggang, et al. High Reliability Analysis of Grounding Fault Signal of 12 kV Primary and Secondary Fusion Switchgear[J]. High voltageapparatus, 2021, 57(10): 158-166+175. DOI: 10.13296/j.1001-1609.hva.2021.10.020.
High Reliability Analysis of Grounding Fault Signal of 12 kV Primary and Secondary Fusion Switchgear
According to the special requirements of the ground fault test signal of the primary and secondary fusion switch
an improved three-point interpolated DFT algorithm to achieve high precision frequency estimation is proposed under the very small cycles in this paper. Based on the maximum sidelobe decay window(MSDW)
the algorithm splits the real and imaginary parts of the DFT spectrum and calculates the three-point interpolation separately.Then the geometric mean calculation is used to eliminate the negative frequency leakage interference. Finally
according to the obtained interpolation formula
the statistical characteristics of the algorithm under noise are strictly mathematical proof. Furthermore
multiple simulations are used to verify the validity and accuracy of the algorithm.The results show that the algorithm can not only maintain relatively stable and high accuracy of correction and estimation under any fluctuation period
but also has strong resistance. Finally
it is applied to the frequency estimation of the measured ground fault waveform signals
which lays the foundation for the accurate reproduction of the input and output ground fault waveform of the 12 kV primary and secondary fusion detection device.