ZHU Lu, WANG Shan, LIU Junxiang, et al. Study on Overvoltage Suppression Method for 500 kV High Coupling Split Reactance Current Limiter[J]. High voltageapparatus, 2021, 57(11): 108-115+123.
DOI:
ZHU Lu, WANG Shan, LIU Junxiang, et al. Study on Overvoltage Suppression Method for 500 kV High Coupling Split Reactance Current Limiter[J]. High voltageapparatus, 2021, 57(11): 108-115+123. DOI: 10.13296/j.1001-1609.hva.2021.11.014.
Study on Overvoltage Suppression Method for 500 kV High Coupling Split Reactance Current Limiter
High Coupling Split Reactance(HCSR)current limiter has good economy and wide applicability and has attracted attention in the field of high-voltage and ultra-high voltage. However
after the introduction of the HCSR current limiter in the power system
its operation process can involve such process as current commutation and the short time introduction of inductance of current limiter into the circuit of the main circuit breaker
which may cause a higher overvoltage. Based on this and in view of such typical scenario as 90 kA short circuit current of 500 k V system
the overvoltage situation of introduced current limiter under different short circuit faults is analyzed and calculated. The suppression result of different over voltage protection schemes to the TRV amplitude and steepness of the main circuit breaker and vacuum fast circuit breaker is compared and analyzed. The results show that
on the basis of parallel capacitance of both ends of the current limiter
the capacitance or resistive capacitance in parallel to the two series vacuum fast circuit breaker can reduce remarkably the steepness and amplitude of TRV of the main circuit breaker
the suppression result of the parallel capacitance to the steepness is more efficient and the suppression result of the parallel resistive capacitance to the amplitude is more remarkable. The research result can provide a basis for the overvoltage protection scheme and parameter selection of the current limiter.
Study on Secondary Arc Current of Four-circuit on the Same Tower Lines of AC 1 000 kV and 500 kV/220 kV
Calculation and Measurement Analysis for Induced Voltage and Current of 500 kV/220 kV Mixed-voltage and Four-circuit Transmission Lines on the Same Tower
Influence of Difference of Three-phase Resistance of Closing Resistor of 750 kV Circuit Breaker on Overvoltage
The Supression Methods of DC Side Harmonic Current and Resonance Overvoltage Adorpted in Zhou-shan DC System
On High-Voltage Engineering Course and Foreign Textbooks
Related Author
TONG Tao
GU Danzhen
CUI Yong
ZHAO Dandan
HUANG Hua
HUANG Shiyang
NING Linru
CHEN Xiao
Related Institution
School of Electrical Engineering,Shanghai University of Electric Power
State Grid Electric Power Research Institute,SMPEC
State Grid Jibei Electric Power Co., Ltd. Electric Power Science Research Institute
State Grid Jibei Electric Power Co., Ltd.
Beijing Power Transmission and Transformation Co., Ltd.