Establishment of 100 kA Impulse Current Standard Measurement System
The impulse current is of transient current waveform and difficult to be assessed due to its short duration
no repetition of waveform and multiple measurement error influence factors. In this paper
the traceability method and uncertainty assessment model of the impulse current measurement device is studied. The standard equipment is developed and measurement uncertainty is reduced as much as possible so to achieve the establishment of 100 kA standard measurement system. The standard system includes current converting device(impulse shunt)and measuring instrument for measurement uncertainty assessment of peak current and time parameters resp
ectively. The uncertainty component
introduced by the dynamic characteristic of the shunt
is evaluated by the step response results. The different evaluation methods of linearity of the shunt are studied
showing that the result is in agreement with the comparison test results of rigid Rogowski coil and those obtained by the temperature rise calculation and evaluation method. The calibration factor and time parameters of the measurement instrument are calibrated by the developed voltage standard wave source. Finally
the performance of the whole system is assessed so to achieve the traceability of impulse current scale factor and time parameter. The measurement uncertainty of the scale factor is4.1×10
-3
(k=2) and of time parameter is 8 ×10
-3
(k=2). The assessment result shows that the measurement accuracy of the established 100 kA impulse current standard measurement device has reached the advanced level.
Study on Calibration of Impulse Current Measuring System
Study on Impulse Voltage Calibrator
Research on Influence of Different Types of Impulse Current on the Aging of ZnO Varistor
Application of Over-compensated Integrators in Impulse Measurements
Study on the Impulse Current for Non-linear Resistances
Related Author
LI He
JIANG Ning
WANG An
REN Wenzhu
YUAN Yuan
LIU Gaojia
LI Wenting
LU Fei
Related Institution
Xi’an High Voltage Apparatus Research Institute Co.,Ltd.
Hubei Electric Power Research Institute
Measurement Research Institute,China Electric Power Research Institute
Xidian Surge Arrester Co., Ltd.
The Wind Solar Storage Division of State Key Laboratory of Control and Simulation of Power System and Generation Equipment, School of Electrical Engineering, Xinjiang University