LI Shan, SUN Bing, HUANG Chen. FCL Calculation Analysis and Site Performance Verification Based on Fast Vacuum Circuit Breaker[J]. High voltageapparatus, 2021, 57(11): 187-195.
DOI:
LI Shan, SUN Bing, HUANG Chen. FCL Calculation Analysis and Site Performance Verification Based on Fast Vacuum Circuit Breaker[J]. High voltageapparatus, 2021, 57(11): 187-195. DOI: 10.13296/j.1001-1609.hva.2021.11.024.
FCL Calculation Analysis and Site Performance Verification Based on Fast Vacuum Circuit Breaker
complicated grid structure and increase of line load have made the short-circuit current exceed the interruption ability of circuit breakers.Therefore
the control of short circuit current exceeds the standard has become a hot topic researched by power grid companies and research institutes. In view of this issue
the principle of FCL device based on fast vacuum circuit breaker is analyzed firstly in this paper;then
the steady and transient simulation model for two sets of FCL devices based on fast vacuum circuit breaker(VCB)
which are installed at one 220 k V power plant in Xinjiang
are set up.The steady short circuit current
the opening and closed operating over-voltage of the fast circuit breaker and its transient recovery voltage are calculated. The calculation result shows that the FCL device can not only limit effectively short circuit current
but also not cause any danger to the system and equipment. Finally
the performance verification test of the FCL is performed at site. The result shows that the FCL device can be able to operate quickly and correctly and such target of the grid fault current limiter as portable structure
low cost
reliable operation and convenient maintenance has been achieved. However
the disadvantage is that there is no artificial short circuit grounding on site
the system has not been short circuit grounding and no actual measurement data is available