LU Xuchen, LI Shuang, TANG Jianeng, et al. Study on Diagnosis Method and Influence Factor of Overheating of Contacts in 550 kV GIS[J]. High voltageapparatus, 2021, 57(11): 220-226.
DOI:
LU Xuchen, LI Shuang, TANG Jianeng, et al. Study on Diagnosis Method and Influence Factor of Overheating of Contacts in 550 kV GIS[J]. High voltageapparatus, 2021, 57(11): 220-226. DOI: 10.13296/j.1001-1609.hva.2021.11.029.
Study on Diagnosis Method and Influence Factor of Overheating of Contacts in 550 kV GIS
For identifying the transient process of internal overheating defect in GIS and infrared imaging diagnosis method
the overheating defect model of contact of 550 kV GIS bus is set up in the laboratory in this paper
the different bad contact conditions are set respectively. The temperature distribution of the fault point and of enclosure under different current is obtained and compared with disconnector and its branch busbar gas compartments in good contact condition. At the same time
the finite element method is adopted to calculate other test conditions which can not be performed in the laboratory. The study result shows that as long as the local temperature of the enclosure is higher than the ambient temperature
it can be clearly observed by infrared image that the influence of the contact resistance
load current and ambient temperature on the temperature rise of the enclosure of the fault point is bigger
while
the type of insulating spacer has no influence on the temperature rise of enclosure of the fault point;Initially
the contact resistance and its generated local high temperature are a linear interaction process.When the temperature is close to the melting point of the conductor
the time from conduction to final melting is very short and this transient process can not be detected by live detection.