Analysis of a Broken on the Charge Shaft of Spring Operating Mechanism for 500 kV Circuit Breaker
In view of breakage of the charge shaft of the spring operating mechanism for 500 k V circuit breaker during the charging period
the physical and chemical inspection on the breakage part is performed and it is confirmed that the breakage of the shaft is not due to the quality of the part. It is found throughout disassembly of the circuit breaker and analysis of the operating principle of the operating mechanism of the circuit breaker during the charging period that insufficient engagement between the cam and the top lever causes the closing spring to drive the charge shaft to“turnback”under the no load condition
which is the cause of the breakage of the charge shaft.