MA Hongming, JIN Shuo, CHENG Zhiwan, et al. Analysis and Treatment on Abnormality of Rupture Disc for High Voltage Switchgear[J]. High voltageapparatus, 2021, 57(11): 232-236.
DOI:
MA Hongming, JIN Shuo, CHENG Zhiwan, et al. Analysis and Treatment on Abnormality of Rupture Disc for High Voltage Switchgear[J]. High voltageapparatus, 2021, 57(11): 232-236. DOI: 10.13296/j.1001-1609.hva.2021.11.031.
Analysis and Treatment on Abnormality of Rupture Disc for High Voltage Switchgear
a batch defect of rupture disc of dead tank circuit breaker is analyzed. It is founded through site detection
fault simulation and performance test that the reason for the abnormal bulge of the protective rubber layer of the rupture disc is due to weak bonding process between the metal rupture disc and protection rubber layer.And the corresponding improvement measures and related suggestions is proposed in accordance with the specific reason of the defect.