Multiphysics Analysis on KYN61-40.5kV High Voltage Switchgear and Study of Insulation Test of Component
Multiple such faults as breakdown of insulation parts and discharge of live conductor to the ground in type KYN61-40.5kV switchgear cabinet at 110 kV substation in Yulin area
China. It is found through investigation at site that there are water droplets on the inner side of the switchgear cabinet and accumulated water in the contact box.Moreover
it is still found during the maintenance process that there is breakdown traces near the outlet of the contact box near the cable room and the cause of the breakdown needs to be explored. Aiming at the condensation and water accumulation phenomenon found in the switchgear cabinet
a three-dimensional simulation model is set up
and the cause for the condensation and the position prone to condensation are found by way of calculating the airflow field and humidity field inside the cabinet. The proposed moisture removal measures of the fan is simulated and verified. The electric field distribution under various condensation conditions is simulated. The insulation withstand voltage test is conducted for the contact box which is prone to condensation. Finally
the scheme to prevent the fault of such switchgear cabinet is proposed in combination with the study result of both simulation and test.