Characteristic and Variation of Noise at 1 000 kV UHV Substation
the 1 000 kV UHV AC substation is taken as an example
the measurement and statistics on the noise of same transformer
HV reactor and filed boundary are performed under the basically identical condition in the consecutive three years. The noise distribution
variation and attenuation feature of the main equipment in the substation are analyzed. The results show that the average noise of main transformer for three consecutive years is 72.9
73.4 and 74.6 dB(A) respectively
with an average increase of 0.6 dB(A) per year. It is concluded through spectrum analysis that the increase of the noise of the main transformer year by year is mainly due to the increase of the noise of the cooling fan. The average noise of the high voltage reactor in the consecutive years is 77.0
77.8 and 79.1 dB(A) respectively
with an average increase of 0.7 dB(A) per year
the average outdoor noise level is 65.7
66.7 and 66.8 dB(A) respectively
with an average increase of 0.4 dB(A) per year and the difference between average indoor and outdoor noise is 9.5~14.1 dB(A). For three consecutive years
the noise variation of substation field boundary is similar and the noise value in the station boundary is small. The noise from the main equipment in the substation has little impact on the surrounding environment.