ZHANG Wenjun, WANG Shuang, CHEN Xiaoyue, et al. Shunt Reactor Configuration of Offshore Wind Farm Transmission System with Submarine Cable[J]. High voltageapparatus, 2022, 58(1): 38-45.
DOI:
ZHANG Wenjun, WANG Shuang, CHEN Xiaoyue, et al. Shunt Reactor Configuration of Offshore Wind Farm Transmission System with Submarine Cable[J]. High voltageapparatus, 2022, 58(1): 38-45. DOI: 10.13296/j.1001-1609.hva.2022.01.006.
Shunt Reactor Configuration of Offshore Wind Farm Transmission System with Submarine Cable
The serious power frequency over voltage of offshore wind power transmission system due to higher charging power of submarine cables can be limited by the use of high-voltage shunt reactor. In this paper
one 220 kV offshore wind farm in China is taken as an example
its power frequency over voltage is calculated theoretically and the transmission system model of offshore wind farm through AC submarine cable is set up by using alternative transient program-electro magnetic transient program(ATP-EMTP). The power frequency over-voltage distribution of offshore wind farm transmission system is calculated
and then the configuration of high voltage shunt reactor is analyzed.The results show that the load dropping over-voltage at the system side is much larger that at the wind farm side. In case of same total compensation degree
the effect of single terminal compensation in land is slightly better than that of double terminal compensation. On this basis
the high voltage reactor configuration of the offshore wind farm to limit power frequency over-voltage is given
and the minimum compensation degree required under different length of submarine cable is calculated
which provides technical basis for engineering design and equipment selection.