ZHAO Yuan, JI Yirun, LIU Yuan, et al. Study on Simulation of Electromagnetic Interference of Flexible DC Converter Valve by Closing Operation of Switch[J]. High voltageapparatus, 2022, 58(1): 130-137.
DOI:
ZHAO Yuan, JI Yirun, LIU Yuan, et al. Study on Simulation of Electromagnetic Interference of Flexible DC Converter Valve by Closing Operation of Switch[J]. High voltageapparatus, 2022, 58(1): 130-137. DOI: 10.13296/j.1001-1609.hva.2022.01.017.
Study on Simulation of Electromagnetic Interference of Flexible DC Converter Valve by Closing Operation of Switch
For exploring the electromagnetic interference characteristic of closing operation of switch to the flexible DC converter valve and as for radiation electromagnetic interference test of closing operation of switch to the flexible DC converter valve
the simulation model is set up in CST simulation software by analyzing the electromagnetic interference principle. The simulation calculation is carried out based on TLM field circuit coupling calculation method.The radiated EMI level of each position in the valve tower in the EMI test is obtained and the influence of electromagnetic interference intensity at different height the shield in valve tower to EMI level is explored. The results show that the peak of radiated EMI spectrum in each position of valve tower basically appears around 0.7 MHz;In general
the height has certain influence on the level of low-frequency EMI
but has little influence on the level of high-frequency EMI. With the increase of height
the variation of electric field intensity amplitude at different positions is inconsistent. The electromagnetic interference of shield is obvious in the positions close to the shield in the valve tower
but is limited at the positions far away from the shield in the valve tower.