Study on Composite Insulation Failure and Electric Field Distribution of Potential Transformer Handcart
Composite insulation is an important insulation mode for compact design of air-insulated switchgears. The operation situation of PT(potential transformer)handcart with composite insulation structure shows that the insulation failure rate of this type of product is high. Specially
under the combined influence of both humidity and contamination
the product with improper insulation structure design likely leads to partial discharge
thus causing interphase short circuit. The reason for it is that the insulation barrier is the“bridge”of interphase short circuit. In this paper
the three-phase fault of one 24 kV PT handcart is analyzed in detail. It can be seen throughout electric field simulation result that in the composite insulation structure
the distance from high voltage to the insulation barrier is the key of the design of composite insulation structure. The fault and electrical field analysis in this paper can provide some useful guidance for new product development and fault diagnosis.