Simulation Study on Temperature Field of Three-phase Enclosed Disconnector Based on Multi-physics Coupling
As an important equipment in urban power grid construction
126 kV GIS needs to be more compact to reduce the footprint of substations. However
the temperature rise is one of the key factors restricting the compactness of the equipment. In this paper
a electromagnetic-thermal-flow coupled coupling 3D model of the 126 kV GIS threephase enclosed disconnector and bus bar is set up
the different power loss generated by different layout of threephase enclosed structure is analyzed through the study of the total heat generation and dissipation of the switcher
and the temperature rise distribution of each part is obtained by the simulation of temperature field.The disconnector and bus bar passed successfully the temperature rise type test in accordance with international standards. Throughout comparison between the simulation and calculation result of the temperature rise
the simulation error is less than 10%.The accuracy of the simulation is verified
which provides effective theoretical and technical support for compact design of three-phase enclosed GIS.