LUO Wei, XIE Chao, CHEN Peilong. Analysis of the Influence Factors of High DC Voltage Measurement Value in Flexible HVDC System and Their Countermeasures[J]. High voltageapparatus, 2022, 58(3): 133-139.
DOI:
LUO Wei, XIE Chao, CHEN Peilong. Analysis of the Influence Factors of High DC Voltage Measurement Value in Flexible HVDC System and Their Countermeasures[J]. High voltageapparatus, 2022, 58(3): 133-139. DOI: 10.13296/j.1001-1609.hva.2022.03.018.
Analysis of the Influence Factors of High DC Voltage Measurement Value in Flexible HVDC System and Their Countermeasures
For improving the stability of flexible HVDC transmission system
auxiliary direct voltage rings are usually installed on the inverting side of flexible DC unit. When the DC voltage between positive and negative poles drops to a certain threshold
the DC voltage is controlled by the inverting side
while the rectifying side transmits the fixed active power and provides reactive power support for the AC system voltage. However
due to the influence of either environment or quality itself
HVDC voltage divider may generate fault and lead to DC voltage fluctuation. In case of abnormal high of the measurement of the rectifying side
the auxiliary direct voltage loop on the inverter side acts which
at this time
causes the both ends of rectifying and converting side of the system to control DC voltage
the transmission power of DC system is out of control and even reversal. In view of this risk
based on RTDS asynchronous networking simulation platform
the abnormal measurement of DC voltage and current is simulated by way of the measurement value multiplying an abnormal coefficient k.The mechanism of power inversion caused by high DC voltage measurement is analyzed
and the corresponding preventive measures are proposed.