KONG Xiangping, LI Peng, XU Kai, et al. Coordination Strategy Analysis Between the DC Line Failure Recovery Function and Neutral Shifting Protection of Converter Transformer[J]. High voltageapparatus, 2022, 58(3): 155-162.
DOI:
KONG Xiangping, LI Peng, XU Kai, et al. Coordination Strategy Analysis Between the DC Line Failure Recovery Function and Neutral Shifting Protection of Converter Transformer[J]. High voltageapparatus, 2022, 58(3): 155-162. DOI: 10.13296/j.1001-1609.hva.2022.03.021.
Coordination Strategy Analysis Between the DC Line Failure Recovery Function and Neutral Shifting Protection of Converter Transformer
The mechanism of neutral shifting protection action of converter transformer in the inverter station after the failure of DC line failure recovery sequence in one site fault case is analyzed in this paper. It is pointed out that the reason of the protection action is that bypass pair of the DC line fault point and the locking operation of rectifier station Z forms a branch loop for the DC current of the healthy pole
causing the arc of the fault point not be interrupted and the bypass pair not be turned off. Then
the bypass pair of inverter station caused by the Y locking operation and the bypass pair of rectifier station form current branch loop again
causing the single phase of the converter transformer to ground and the neutral shifting protection to trip. Furthermore
the improvement measures which can prevent the development of the current branch loop and the trip of converter transformer neutral shifting protection are proposed by taking the operating condition of the DC transmission project into consideration.