Research on Capacitive Current Interruption Capability of Circuit Breaker
has become the key index of circuit breaker meeting the engineering requirements. Due to the high risk of test failure caused by re-striking during the interruption period
it is necessary to assess its capacitive interruption capability. Based on the characteristics of capacitive current
the“recovery voltage”and“minimum critical voltage”are used in this paper to assess its capacitive current interruption capability. And the circuit breaker
in case that the“recovery voltage”is lower than“minimum critical voltage”
has the ability to interrupt break capacitive current. The interruption performance of circuit breaker is assessed by using the coupling analysis method of electric field and air(gas)flow field
the“the recovery voltage”is lower than the“minimum critical voltage”is obtained
which indicates that the circuit breaker has the capability to interrupt the capacitive current and passed successfully test verification at grade C2. It shows further the feasibility of adopting“ the minimum critical voltage”to assess the capacitive current interruption capability of circuit breaker and provides a reference for the design of circuit breaker interrupting the capacitive current.