Analysis on Frequent Pumping of Hydraulic Spring Operating Mechanism for500 kV Circuit Breaker
the hydraulic spring operating mechanism for high voltage circuit breaker may appear such problems during the operation as locking
maloperation
refusal operation
unable charging and frequent pumping etc. In this paper
based on the frequent pumping of hydraulic operating mechanism for 5061 circuit breaker of 500 kV H substation
it is found after the disassembly of the operating mechanism that some long penetrated cracks are existed at high and low pressure conversion oil passage hole wall in the inner wall of the working cylinder. It is presumed through stress analysis by way of modeling and such test results as non-destructive inspection
metallographic structure and electron microscopy analysis that the high and low pressure oil passage hole wall in working cylinder is cracked due to stress corrosion
which leads to the leakage of high pressure hydraulic oil to the low pressure hydraulic oil pipeline during operation
thus causing frequent pumping of the mechanism. On this basis
the same type of mechanism is selectively inspected in combination with power outage plan
the manufacturer is recommend to strengthen process control to prevent occurrence of similar phenomena and ensure stable operation of power system.