LI Guangmao, LI Xiao, DU Gang, et al. Influence of Demp Heat Aging on Withstand Characteristics of Inter-turn Overvoltage of Reactor[J]. High voltageapparatus, 2022, 58(6): 98-103.
DOI:
LI Guangmao, LI Xiao, DU Gang, et al. Influence of Demp Heat Aging on Withstand Characteristics of Inter-turn Overvoltage of Reactor[J]. High voltageapparatus, 2022, 58(6): 98-103. DOI: 10.13296/j.1001-1609.hva.2022.06.014.
Influence of Demp Heat Aging on Withstand Characteristics of Inter-turn Overvoltage of Reactor
In the operation process of dry-type air-core reactors
moisture may invade the package
cause serious demp heat aging of the insulation inside the package
and eventually result in reactor accidents. However
at present the detailed process and mechanism of the demp heat aging and the fire failure of reactor have not been studied in depth. Due to the deterioration of the breakdown performance of the demp heat aging materials
the inter-turn insulation may be broken down under the action of overvoltage to form a permanent inter-turn short-circuit path and malfunction. In this paper
the possibility of such short-circuit failures is discussed and the influence of the inter-turn overvoltage on the inter-turn insulation is studied. First
the maximum overvoltage that may appear at the reactor port is analyzed. Then
the chain loop is used to calculate the maximum inter-turn overvoltage that the reactor may suffer during operation. Finally
a special reactor model containing only two turns is used to study the risk of inter-turn insulation fault by the inter-turn overvoltage. The results show that although the inter-turn insulation of the reactor
in case of suffering the overvoltage shock
is likely to withstand a large overvoltage
yet the overvoltage is not easy to damage the inter-turn insulation and lead to short circuit failure even if the inter-turn insulation is seriously aged.