ZHANG Youfeng, ZHENG Yunhong, DAI Dongyun, et al. Research on Influence of Temperature on Metering Accuracy of Electronic Voltage Transformer[J]. High voltageapparatus, 2022, 58(6): 221-227+236.
DOI:
ZHANG Youfeng, ZHENG Yunhong, DAI Dongyun, et al. Research on Influence of Temperature on Metering Accuracy of Electronic Voltage Transformer[J]. High voltageapparatus, 2022, 58(6): 221-227+236. DOI: 10.13296/j.1001-1609.hva.2022.06.031.
Research on Influence of Temperature on Metering Accuracy of Electronic Voltage Transformer
Since the ambient temperature will interfere with Electronic Capacitive Voltage Transformer(ECVT)used for outdoor pole switches and reduce its metering accuracy
the specific influence of temperature change on its metering accuracy during operation of ECVT is studied in combination with the test circuit in this paper. The product characteristics of high-voltage capacitors in domestic are studied and analyzed firstly in this paper. After comparison
high-voltage ceramic capacitors made of NP0 material are selected as the tested capacitors. Secondly
the ECVT precision test circuit
which is applicable for the primary and secondary fusion requirement
is designed. And a kind of improved capacitance error test scheme is proposed in accordance with China National Standard and field test structure. The test results show that on the basis of this test method and in case of ambient temperature variation within-40~70 ℃
the accuracy of the tested high-voltage capacitors can reach the 0.5 level standard required by the State Grid Corporation of China and it
however
is difficult to reach the more sophisticated 0.2 level standard requirement.