ZHANG Dandan, CHEN Junqin, YANG Ruilin. Analysis of New Grounding Mode for Neutral Point of Giant Hydro-generator[J]. High voltageapparatus, 2023, 59(1): 1-7.
DOI:
ZHANG Dandan, CHEN Junqin, YANG Ruilin. Analysis of New Grounding Mode for Neutral Point of Giant Hydro-generator[J]. High voltageapparatus, 2023, 59(1): 1-7. DOI: 10.13296/j.1001-1609.hva.2023.01.001.
Analysis of New Grounding Mode for Neutral Point of Giant Hydro-generator
The main grounding method adopted by the hydroelectric generators has such two modes as grounding through the arc suppression coil and through high resistance of distribution transformer. However
with the increase of capacity of generator
it is difficult for these two grounding modes to control the fault current and the transient overvoltage within the standard range simultaneously. In this paper
a giant hydro-generator is taken as the object
the innovative combined grounding mode of resistance with compensation reactance is studied. First
the value interval of resistance and reactance of the grounding mode of“resistance and reactance in series”and“resistance and reactance in parallel”under short circuit limit is obtained by theoretical derivation. Then
the transient over-voltage under 4 different types of grounding modes is calculated by setting up MATLAB/Simulink simulation model. The results show that under the same short circuit current limit
the effect of suppressing transient over-voltage by the grounding mode of resistance and reactance in parallel is better than that of series mode
which can be limited in the standard range.The detuning degree
in case of adopting shunt grounding mode
can be decreased
but the displacement over-voltage will increase.The research can provide a reference for the neutral grounding mode of giant hydro-generators.