Calculation and Analysis of Multiple Reignition Arc Model of Disconnector in GIS
disconnector can generate very fast transient over-voltage(VFTO)during operation. The accurate arc model of disconnector plays a key role in the simulation of the fast transient over-voltage. In this paper
based on the segmented arc
ATP-EMTP software is used to set up the multiple re-ignition arc model of disconnector. For studying the influence of residual charge on VFTO at the load end
a number of residual voltages with different amplitudes are selected.The simulation results show that the amplitude of VFTO harmonic generated by the multiple reignition arc model based on segmented arc is larger than that of the traditional time-varying resistance arc model.The number of breakdown of disconnector gap will increase with the increase of residual voltage amplitude on the load side. The maximum value of VFTO on both sides of disconnector and inlet of transformer will not cause insulation breakdown.The relevant data is of great significance for the insulation design of substation.