ZENG Huarong, MAO Xianyin, YANG Qi, et al. Study on Discharge Mechanism and Test of Tree Adjacent Conductor in Overhead Transmission Line Corridor[J]. High voltageapparatus, 2023, 59(1): 64-69.
DOI:
ZENG Huarong, MAO Xianyin, YANG Qi, et al. Study on Discharge Mechanism and Test of Tree Adjacent Conductor in Overhead Transmission Line Corridor[J]. High voltageapparatus, 2023, 59(1): 64-69. DOI: 10.13296/j.1001-1609.hva.2023.01.010.
Study on Discharge Mechanism and Test of Tree Adjacent Conductor in Overhead Transmission Line Corridor
Tree barrier is an important cause of line trip and even blackout of power grid. It is of great significance to study the partial discharge mechanism of the conductor near the tree for the early warning and prevention of tree barrier. The partial discharge test platform of the conductor near the tree is set up. The high-frequency discharge current
power frequency voltage
and ultraviolet as well as visible images of the test circuit are comprehensively monitored. The influence of environmental humidity
crown shape and moisture on the discharge characteristics are studied. The research results show that the discharge form and development process of tree-conductor are closely related to such factors as the moisture of trees and the speed of wires near the trees. And the discharge has such three forms as direct breakdown flashover
intense discharge without arcing and stable arcing without flashover. For the latter two kinds of discharge forms
the pre-discharge current at the average amplitude up to 40~500 mA
the wave head time at0.17~0.88 μs and the wave tail time at 1.42~6.81 μs can be generated. The conclusion of the study lays a theoretical foundation for the monitoring and early warning of the discharge of the actual transmission lines near the trees.