Explosion Accident Analysis and Prevention of Resonance Overvoltage of 35 kV Potential Transformer
the ferromagnetic resonance phenomenon frequently occurs under certain conditions due to the non-linear characteristics of the excitation inductance of the electromagnetic potential transformer(PT). In this paper
the occurrence process and the cause of the accident are studied in combination with the field data of a 35 kV electromagnetic PT explosion accident and the use of ATP-EMTP software modeling and simulation analysis. Considering the actual operation status of the substation
the effective harmonic elimination measures and its optimization strategy are proposed. The analysis and study show that the reason of the accident is that when the semi-insulating PT performs harmonic elimination in the non-linear resistance resonance eliminator of the neutral point of primary side with D-parameter discharge tube
the discharge tube has the risk of not normal operation
resulting in breakdown discharge of the neutral point of the primary side to the secondary terminal and ground and causing frequency division ferromagnetic resonance. The way of connecting harmonic eliminator at the neutral point of the primary side of fully insulated PT has best effect of suppressing such accident. Finally
an effective optimization strategy for resonance elimination scheme is proposed.