LI Hongbing, WU Chuanqi, ZHANG Hong, et al. Failure Analysis on Rupture Disc of 220 kV GIS[J]. High voltageapparatus, 2023, 59(1): 192-197.
DOI:
LI Hongbing, WU Chuanqi, ZHANG Hong, et al. Failure Analysis on Rupture Disc of 220 kV GIS[J]. High voltageapparatus, 2023, 59(1): 192-197. DOI: 10.13296/j.1001-1609.hva.2023.01.027.
Rupture disc for GIS is an important pressure relief device to prevent GIS equipment from explosion due to sudden increase of gas pressure inside GIS equipment. The selection of its position and design of parameters are closely related to internal arcing fault of GIS. In view of mal-operation of rupture disc of 220 kV GIS
the selection basis of gas compartment and design parameters selection of rupture disc of GIS at different voltage levels are analyzed on the basis of principle of internal pressure increase inside the enclosure due to fault arc inside GIS. The serious mistake in the design of rupture disc of GIS equipment is described. The conclusion of the analysis is of great significance for the type selection and acceptance of rupture disc for GIS equipment.