Infrared Analysis of Nonlinear Heating Characteristics of Deteriorated Porcelain Insulator of 500 kV Transmission Lines
Deteriorated parts of insulator stings in high voltage transmission lines can constitute a threat to the safety of power grid. For studying the infrared heating characteristics of deteriorated porcelain insulator
a series of experiments aer set up to study the influence of the deteriorated insulator’s resistance
location along the strings and environmental relative humidity on infrared detection. Moreover
additional experiments are carried out on a string containing two pieces of deteriorated insulators to investigate the different heating phenomena between normal and low-resistance insulators. The heating mechanism of the steel cap in the infrared image is analyzed further by using the finite element analysis simulation. The experimental and simulation results show that the relationship between temperature rise of deteriorated insulator and its impedance is nonlinear
the max rise will be reached when the resistance is 30 MΩ; the deterioration on both ends of the insulator string are easy to be detected; the excessive high relative humidity may lead to incorrect detection; the heating area of normal insulator is at the lower part of its steel-cap and temperature of its porcelain rises by approximately 1.2 ℃. As for deteriorated insulators
the temperature rise along its steel-cap is evenly distributed
and its porcelain remains almost the same temperature as being tested before. The related study results have provided a reference for the infrared detection of deteriorated insulators.
Research on Temperature Distribution Characteristic of Transformer Based on Finite Element Method
Optimization Design on Spring Contact Finger Structure Based on Finite Element Method and Neural Network Method
Influence of Contamination on Voltage Monitoring Board for Light Triggered Thyristor Converter Valve and the Corresponding Countermeasures
Operation Characteristic Analysis of Permanent Electromagnet for Spring Mechanism
Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
Related Author
XIE Zhibiao
WANG Chen
CHEN Liangyuan
HUANG Pei
HE Shijian
ZHOU Song
SU Juntian
DAN Shuheng
Related Institution
Hechi Power Supply Bureau of Guangxi Power Grid Co., Ltd.
Electric Power Science Research Institute of Guangxi Power Grid Co., Ltd.
College of Electrical Engineering, Shanghai University of Electric Power
State Grid Nanjing Power Supply Company
Shenzhen International Graduate School, Tsinghua University