ZHANG Jiaqing, XIE Jia, HUANG Weimin, et al. Study on Optimal Design of Automatic Fire Extinguishing Device for Failure of High Voltage Switchgear Cabinet[J]. High voltage apparatus, 2024, 60(1): 41-47.
DOI:
ZHANG Jiaqing, XIE Jia, HUANG Weimin, et al. Study on Optimal Design of Automatic Fire Extinguishing Device for Failure of High Voltage Switchgear Cabinet[J]. High voltage apparatus, 2024, 60(1): 41-47. DOI: 10.13296/j.1001-1609.hva.2024.01.005.
Study on Optimal Design of Automatic Fire Extinguishing Device for Failure of High Voltage Switchgear Cabinet
multiple fire accidents of high voltage switchgear cabinet have happened. The fire extinguishing of traditional switchgear cabient is performed manually
which has such problems as low efficiency and high risk. The study of automatic fire extinguishing device for existing high voltage switchgear cabinet has such problems as electric field distortion
unclear starting threshold and improper selection of fire extinguishing agent. For solving above problem
the study of automatic fire extinguishing system is developed in this paper. Firstly
the sprinkler structure of fire extinguishing agent is optimized so to reduce the maximum electrical field strength and avoid dielectrci breakdown risk. Then
a fire simulation test of true switchgear cabinet is carried out
and the starting threshold of fire extinguishing device is determined based on the temperature field distribution during the test. Moreover
type and dosage of the extinguishing agent are studied
and a reasonable extinguishing agent setting scheme for high voltage switchgear cabinet is determined. A complete automatic fire extinguishing system of high voltage switchgear cabinet is set up. The test results show that the developed fire extinguishing system is fast and effective.