CHEN Lei, WU Chengwei, LI Ao, et al. Electrical Endurance Assessment System of SF6 Circuit Breaker for Switching Capacitor Bank Based on Current Monitoring and Dynamic Resistance Analysis[J]. High voltage apparatus, 2024, 60(1): 55-62.
DOI:
CHEN Lei, WU Chengwei, LI Ao, et al. Electrical Endurance Assessment System of SF6 Circuit Breaker for Switching Capacitor Bank Based on Current Monitoring and Dynamic Resistance Analysis[J]. High voltage apparatus, 2024, 60(1): 55-62. DOI: 10.13296/j.1001-1609.hva.2024.01.007.
Electrical Endurance Assessment System of SF6 Circuit Breaker for Switching Capacitor Bank Based on Current Monitoring and Dynamic Resistance Analysis
circuit breakers for switching capacitor bank is of great significance to ensure safe and reliable operation of power grid. In this paper
the contact wear calculation method
and dynamic resistance analysis method are combined to assess the electrical endurance of SF
6
circuit breaker
and the criteria base of electrical endurance of SF
6
circuit breaker is proposed. Firstly
the circuit breaker contact wear is calculated based on the current monitoring data of the circuit breaker
and the electrical endurance of the circuit breaker electrical is judged and predicted. Then the real condition of SF
6
circuit breaker is verified by dynamic resistance analysis method. Both the real-time performance of contact wear calculation method and the accuracy of dynamic resistance method are also considered. Based on the proposed criteria
a set of electrical endurance assessment system of SF
6
circuit breaker integrating contact wear and dynamic resistance is developed. The system can accurately assess the electrical endurance of SF
6
circuit breakers based on the switching data and dynamic resistance and
at the same time
visually present the results on the human-computer interaction interface
providing auxiliary decision for the staff to perform the maintenance of circuit breaker.