Monitoring and Protection on Inter-turn Short Circuit Fault for Reactor of High Pass 3rd-order AC Filter in DC Convert Station
Research & Analysis|更新时间:2025-04-26
|
Monitoring and Protection on Inter-turn Short Circuit Fault for Reactor of High Pass 3rd-order AC Filter in DC Convert Station
High Voltage ApparatusVol. 60, Issue 1, Pages: 136-143(2024)
作者机构:
1.天津经纬正能电气设备有限公司,天津 300353
2.国网浙江省电力有限公司电力科学研究院,杭州 310014
3.湖南大学,长沙 410082
作者简介:
基金信息:
Science and Technology Project of State Grid Corporation(5500-202119131A-0-0-00);Young Elite Scientists Sponsorship Program by CAST Under Grant(2021QNRC001);Hunan Natural Science Foundation(2021JJ20013);Science and Technology Innovation Program of Hunan Province(2021RC3058)
JIA Genmao, ZHAO Qicheng, LUO Fuquan, et al. Monitoring and Protection on Inter-turn Short Circuit Fault for Reactor of High Pass 3rd-order AC Filter in DC Convert Station[J]. High voltage apparatus, 2024, 60(1): 136-143.
DOI:
JIA Genmao, ZHAO Qicheng, LUO Fuquan, et al. Monitoring and Protection on Inter-turn Short Circuit Fault for Reactor of High Pass 3rd-order AC Filter in DC Convert Station[J]. High voltage apparatus, 2024, 60(1): 136-143. DOI: 10.13296/j.1001-1609.hva.2024.01.016.
Monitoring and Protection on Inter-turn Short Circuit Fault for Reactor of High Pass 3rd-order AC Filter in DC Convert Station
The inter-turn short circuit of reacotr in high pass 3rd-order (HP3) AC filter bank in DC converter station occurs frequenctly which
due to the lak of fast monitoring and protection of the fault
causes the inter-turn short circuit to sustain for 3 to 9 miuntes and buring. After the inter-turn short circuit
the equivalent inductance of the reactor will decrease continuously
which causes variation of filter circuit parameters and further causes the thermal overload protection startup alarm of the filter configuration. Long term fault will also cause the secondary reactor bottom support insulator flashover grounding
causing the filter differential protection action outlet to trip. In this paper
three typical fault cases are analyzed
and the reasons for the start and action of the protection in combination with the design concept and operation characteristics of type C HP3 filter are explained. As for such characteristic that the power frequency voltage and current increase with the uniterupted development of inter-turn short circuit on reactor of HP3 circuit due to inter-turn short circuit
a kind of fault monitoring and protection method based on the power frequency voltage differential principle is proposed.