Analysis on Electromagnetic Interference of Short Circuit Current to Secondary Equipment and Research on Anti-interference Measures
Technical Discussion|更新时间:2025-04-26
|
Analysis on Electromagnetic Interference of Short Circuit Current to Secondary Equipment and Research on Anti-interference Measures
High Voltage ApparatusVol. 60, Issue 1, Pages: 182-189(2024)
作者机构:
1.国网呼伦贝尔供电公司,内蒙古 呼伦贝尔 021100
2.郑州大学电气工程学院,郑州 450000
3.河南省输配电装备与电气绝缘工程技术研究中心,郑州 450000
作者简介:
基金信息:
National Natural Science Foundation of China(51977195;51777025);Key Scientific Research Projects of Colleges and Universities in Henan(16A470014;19A470008)
ZHANG Ying, YUAN Xiaodong, CAO Chuncheng, et al. Analysis on Electromagnetic Interference of Short Circuit Current to Secondary Equipment and Research on Anti-interference Measures[J]. High voltage apparatus, 2024, 60(1): 182-189.
DOI:
ZHANG Ying, YUAN Xiaodong, CAO Chuncheng, et al. Analysis on Electromagnetic Interference of Short Circuit Current to Secondary Equipment and Research on Anti-interference Measures[J]. High voltage apparatus, 2024, 60(1): 182-189. DOI: 10.13296/j.1001-1609.hva.2024.01.021.
Analysis on Electromagnetic Interference of Short Circuit Current to Secondary Equipment and Research on Anti-interference Measures
the construction of smart distribution network is continuously promoted
which speeds up the development of related technologies of primary and secondary equipment of distribution switch
and
however
higher requirement of the secondary equipment under the long term and complicated electromagnetic environment is put forward. In this paper
the test platform of the electromagnetic interference of short circuit current to the secondary equipment of distribution switch is set up on the basis of synthetic test circuit. The study on the influence of the related interference of the breaking fault current on the complete set equipment is developed
the reason of interference signal genration and also the spectrum characteristic are analyzed. As for the interference characteristic
a set of anti-interference measurement system is designed
the ATP-EMTP is used to simulate synthetic circuit for simulation analysis and actual test verification. The results show that in case of breaking test of the complete set equipment the secondary equipment port will be disturbed greatly. The current waveform will also be distorted
the maximum interference current can be up to 26 A and the interference current is affected by the magnetic saturation and desaturation of the current transformer. With addition of the anti-interference measures
the output accuracy of the secondary equipment is increased by about 40% over the previous one. The test resutl this time can provide related evidence for the electromagnetic compability study of the secondary equipment of the primary and secondary fusion complete set complete set equipment.