Application of X-ray Measurement Size Calibration Technology in Defect Detection of GIS
Research & Analysis|更新时间:2025-04-26
|
Application of X-ray Measurement Size Calibration Technology in Defect Detection of GIS
High Voltage ApparatusVol. 60, Issue 6, Pages: 27-32(2024)
作者机构:
1.国网安徽省电力有限公司电力科学研究院,合肥 230601
2.国网安徽省电力有限公司,合肥 230601
3.合肥工业大学,合肥 230009
4.中国科学院电工研究所,北京 100190
作者简介:
基金信息:
Science and Technology Projects of State Grid Anhui Electric Power Company Limited Research Institute(52120523000M);Science and Technology Project of SGCC(5500-202135125A-0-0-00)
ZHANG Guobao, YANG Wei, ZHAO Hengyang, et al. Application of X-ray Measurement Size Calibration Technology in Defect Detection of GIS[J]. High voltage apparatus, 2024, 60(6): 27-32.
DOI:
ZHANG Guobao, YANG Wei, ZHAO Hengyang, et al. Application of X-ray Measurement Size Calibration Technology in Defect Detection of GIS[J]. High voltage apparatus, 2024, 60(6): 27-32. DOI: 10.13296/j.1001-1609.hva.2024.06.004.
Application of X-ray Measurement Size Calibration Technology in Defect Detection of GIS
GIS equipment in service is compact in layout and complex in structure. The shooting angle of the X -ray is limited due to such constrains as space
height and testing tools. Such non-vertical irradiation situations as center deviation of beam and detector flipping often occur
and the X-ray testing spectrum shows such deformation as translation and stretching
resulting in significant measurement errors in dimension of GIS component and difficulty in accurately identifying some defects. In view of above typical issues
the geometric models for vertical irradiation such as X-ray beam center offset
detector flipping
and non-vertical irradiation such as X-ray beam center offset and detector flipping are set up. The influence of X-ray beam center offset and detector flipping angle on the size of X-ray detection spectra is studied
the calibration formula for X-ray detection spectra under different non vertical irradiation condition is proposed
a calibration method for defect size measurement in the operating GIS using X-ray detection under non-vertical irradiation condition is developed and achieving measurement and calibration of defect size under full transmission conditions is achieved. The relevant research results have achieved good application results in the diagnosis and characterization of defects in ultra-high voltage GIS disconnector at site.