DAI Dongyun, LIU Shuquan, YOU Yimin, et al. Electric Field Analysis and Optimization Design of Insulation Structure of 12 kV Vacuum Interrupter[J]. High voltage apparatus, 2024, 60(6): 50-56.
DOI:
DAI Dongyun, LIU Shuquan, YOU Yimin, et al. Electric Field Analysis and Optimization Design of Insulation Structure of 12 kV Vacuum Interrupter[J]. High voltage apparatus, 2024, 60(6): 50-56. DOI: 10.13296/j.1001-1609.hva.2024.06.007.
Electric Field Analysis and Optimization Design of Insulation Structure of 12 kV Vacuum Interrupter
Due to the local breakdown phenomenon inside the porcelain shell during the power frequency voltage burn-in test of 12 kV vacuum interrupter
it is necessary to study its internal structure to find an insulation optimization solution to improve the internal potential distribution of the interrupter. In this paper
a three-dimensional electric field calculation model is set up based on the actual size of the vacuum interrupter
and the electric field distribution of each part is obtained by finite element calculation. The insulation strength of the moving and stationary contacts as well as the shield of the vacuum interrupter is analyzed. According to the calculation results
the edge fillet
radius and slot width of the contact piece are optimized and the structure of the shield is improved. The electric filed analysis is performed on the basis of the optimization scheme. Finally
the optimized prototype passed the power frequency voltage burn-in test verification.