Electric Field Analysis and Calculation of Parallel Capacitors for 252 kV Environment-friendly GIS Double-break Vacuum Circuit Breaker
This article designs two new types of 252 kV environmentally friendly GIS double break vacuum circuit breaker voltage sharing structures
the two different equalizing methods are adopted
namely
one capacitor is connected in parallel at each break of the double-break vacuum interrupter
or two capacitors are connected in parallel at each break
comparative analysis of electric field values calculated by different voltage equalization methods
the influence of different voltage equalization methods on the electric field of the main components of the double break vacuum circuit breaker has been obtained. The calculation results show that: the voltage equalization method of parallel single capacitor in the vacuum arc-extinguishing chamber only reduces the non-uniformity coefficient between the breaks
however it will lead to excessive electric field strength of the shielding cover and the contact
the voltage equalization method of two single capacitors connected in series not only reduces the non-uniformity coefficient of the fracture
but also reduces the potential difference between the suspended shielding cover in vacuum interrupter
making the potential distribution more uniform
reducing the field strength value of the shielding cover and contacts
relative to the voltage equalization method of parallel single capacitorsand the maximum electricfield strength is reduced by 25.78%.