XIE Cheng, SHAO Xianjun, DING Wuxing, et al. On-line Monitoring of the Density of Environmentally Friendly Insulating Medium C4F7N/CO2 Gas Mixture[J]. High voltage apparatus, 2024, 60(9): 141-147.
DOI:
XIE Cheng, SHAO Xianjun, DING Wuxing, et al. On-line Monitoring of the Density of Environmentally Friendly Insulating Medium C4F7N/CO2 Gas Mixture[J]. High voltage apparatus, 2024, 60(9): 141-147. DOI: 10.13296/j.1001-1609.hva.2024.09.019.
On-line Monitoring of the Density of Environmentally Friendly Insulating Medium C4F7N/CO2 Gas Mixture
mixed insulating gas is an important factor that determines its insulation performance
so real-time monitoring of the C
4
F
7
N mixed gas density is particularly important. The temperature-pressure characteristic of C
4
F
7
N/CO
2
mixed gas is the basis for studying its density monitoring and verification. Therefore
this paper mainly studies the temperature-pressure characteristics of C
4
F
7
N/CO
2
gas with different mixing ratios at a density of 0.12 MPa
and compares them with the theoretical calculation results of the ideal gas state equation and the SF
6
gas state equation. The error is within ±1%. Tests have proved that
at a low density 0.12 MPa
the gas characteristics of C
4
F
7
N/CO
2
with different mixing ratios are approximately in line with the ideal gas state equation. Where the accuracy of density detection is not strictly required
a traditional SF
6
gas density relay can be install
ed to monitor the density of C
4
F
7
N/CO
2
mixed gas. According to the temperature-pressure characteristics of the C
4
F
7
N/CO
2
mixed gas
an online monitoring device for the density of the C
4
F
7
N/CO
2
mixed gas and its calibration instrument can be developed.