XIE Cheng, SHAO Xianjun, ZHANG Wei, et al. Research on Humidity Detection Technology of C4F7N/CO2 Mixture[J]. High voltage apparatus, 2024, 60(9): 148-154.
DOI:
XIE Cheng, SHAO Xianjun, ZHANG Wei, et al. Research on Humidity Detection Technology of C4F7N/CO2 Mixture[J]. High voltage apparatus, 2024, 60(9): 148-154. DOI: 10.13296/j.1001-1609.hva.2024.09.020.
Research on Humidity Detection Technology of C4F7N/CO2 Mixture
mixed insulating gas in electrical equipment affect the insulation perfo
rmance of the gas. Regularly checking this humidity is one of the daily operation and maintenance tasks. In this paper
different humidity C
4
F
7
N/CO
2
mixed insulating gas is detected by chilled-mirror dew point meter and capacity-resistance hygrometer commonly used in the daily operation and maintenance of substation
and the experiments indicate that conventional humidity monitors mentioned above are not able to be used for C
4
F
7
N/CO
2
mixture humidity detection directly. The chilled-mirror dew point meter above is modified technically and the accuracy tests are did using standard humidity C
4
F
7
N/CO
2
mixture in this paper. The results show that the dew point measurement error of the modified chilled-mirror dew point meter is less than ±0.2 ℃
and it can accurately measure humidity of no less than 150 μL/L when the C
4
F
7
N proportion is not more than 12%
which meet the operation and maintenance requirements of the electrical equipment insulated with C
4
F
7
N/CO
2
mixture. The capacity-resistance hygrometer above after recalibration using C
4
F
7
N/CO
2
mixture humidity generator can be used for C
4
F
7
N/CO
2
mixture humidity detection
with a dew point detection error of no more than ±2.0 ℃.