ZHANG Changhong, YANG Xu, LI Weiguo, et al. Optimization and Application of High Precision Separation and Multi-channel Continuous Measurement Technology for SF6 Components[J]. High voltage apparatus, 2024, 60(9): 179-187.
DOI:
ZHANG Changhong, YANG Xu, LI Weiguo, et al. Optimization and Application of High Precision Separation and Multi-channel Continuous Measurement Technology for SF6 Components[J]. High voltage apparatus, 2024, 60(9): 179-187. DOI: 10.13296/j.1001-1609.hva.2024.09.024.
Optimization and Application of High Precision Separation and Multi-channel Continuous Measurement Technology for SF6 Components
Sulfur hexafluoride gas insulated power equipment (hereinafter referred to as SF
6
equipment) has been widely used because of its excellent insulation
arc extinguishin
g performance
small footprint
high reliability
safety
small maintenance workload and many other advantages. Many factors may lead to insulation defects in SF
6
equipment during installation and operation. Measuring the content of typical decomposition products in SF
6
gas in the equipment is one of the most effective detection methods to judge insulation defects. In order to detect the decomposition products of SF
6
gas
off-line instruments are usually used to conduct regular inspection of SF
6
equipment in substations. This method has few detection components and poor real-time performance. Usually
the abnormal gas components can be detected after the equipment failure
so it can not prevent the latent failure of the equipment in advance. In this paper
a technology of high-precision separation and multi-channel continuous measurement of SF
6
gas decomposition products is proposed
which solves the technical problems such as unstable gas flow
low efficiency of single channel detection and inability to remotely carry out chromatographic sampling and analysis in the process of long-time monitoring. Compared with the traditional off-line detection methods
this method has more detection components
remote real-time monitoring
good long-time monitoring stability and higher monitoring efficiency
which fills the deficiency of gas chromatography monitoring method in the field of SF
6
gas on-line monitoring. By continuously monitoring the content of more than 10 characteristic gas components in SF