WANG Yang, HAN Wei, HUANG Lianpeng, et al. Fourier Transform Infrared Spectrum Analysis of Free Gas in Power Transformer[J]. High voltage apparatus, 2024, 60(11): 86-93.
DOI:
WANG Yang, HAN Wei, HUANG Lianpeng, et al. Fourier Transform Infrared Spectrum Analysis of Free Gas in Power Transformer[J]. High voltage apparatus, 2024, 60(11): 86-93. DOI: 10.13296/j.1001-1609.hva.2024.11.010.
Fourier Transform Infrared Spectrum Analysis of Free Gas in Power Transformer
In view of the issue that the gas chromatography analysis of free gas in power transformer needs manual gas extraction and long time consumption at present
a kind of on-line monitoring method of free gas by Fourier infrared spectrum is proposed in this paper. The works of the gas collector connected with the gas relay is controlled through the solenoid valve and free gas is automatically taken from the gas collector for spectral analysis. In the process of free gas spectral analysis
the segmented ratio baseline correction method is used to correct the the absorption spectra of free gas
and the Tikhonov regularized characteristic variable method is used to select the feature variables from the miscellaneous spectrum lines of the absorption spectrogram of the free gas. Finally
the least squares support vector machine method is used to set up quantitative analysis models
analyze and calculate infrared spectrogram and get the volume fraction concentration of each component in the free gas of power transformer. The laboratory experiment results show that the Fourier infrared spectrum on-line monitoring system for free gas of power transformer can complete automatic gas extraction and gas detection of free gas
realize the on-line monitoring of free gas and high-precision detection of multi-component free gas. And the work introduced in this paper has practical application value.