Study on Electromagnetic Transient Characteristics During Switching Operation of 750 kV GIS Substation
For clarifying the electromagnetic transient characteristics during the switching operation of gas insulated switchgear (GIS)
the measurement scheme is designed to measure the transient enclosure voltage (TEV) and the transient ground potential rise (TGPR) under such two types of operations as single close operation of disconnector and circuit breaker during the operation of one 750 kV GIS. And the measurement results of the two types of operations are compared and analyzed from the macro-pulse and micro-pulse characteristics aspects. The results show that the maximum values of TEV and TGPR are 22.8 kV and 19.6 kV
respectively
and TGPR is higher than TEV at many measuring points. Compared to the closed operation of circuit breaker
the electromagnetic oscillation energy generated by the closed operation of disconnector is small
but the duration of macro pulse is long and number of breakdown is more.