Vibration Response Analysis of 220 kV Mobile Load Transfer Device Based on Ansys Workbench
Research & Analysis|更新时间:2025-04-26
|
Vibration Response Analysis of 220 kV Mobile Load Transfer Device Based on Ansys Workbench
High Voltage ApparatusVol. 60, Issue 11, Pages: 217-224(2024)
作者机构:
1.国网电力科学研究院有限公司, 南京 211106
2.国网电力科学研究院武汉南瑞有限责任公司, 武汉 430074
3.国网湖北省电力有限公司超高压公司, 武汉 430050
作者简介:
基金信息:
Science and Technology Project of SGCC (Research and Application of Emergency Power Transfer Technology for Outage Maintenance of 220 kV Switch Bay Equipment in Substation)
QUAN Jianghua, WEN Zhengqi, ZHANG Wei, et al. Vibration Response Analysis of 220 kV Mobile Load Transfer Device Based on Ansys Workbench[J]. High voltage apparatus, 2024, 60(11): 217-224.
DOI:
QUAN Jianghua, WEN Zhengqi, ZHANG Wei, et al. Vibration Response Analysis of 220 kV Mobile Load Transfer Device Based on Ansys Workbench[J]. High voltage apparatus, 2024, 60(11): 217-224. DOI: 10.13296/j.1001-1609.hva.2024.11.026.
Vibration Response Analysis of 220 kV Mobile Load Transfer Device Based on Ansys Workbench
The 220 kV mobile load transfer device is used to fix and the install the combined electrical equipment on the load-carrying vehicle
which will inevitably be subjected to the vibration and shock during the automobile transportation for a long time. In this paper
the Ansys Workbench finite element analysis platform is used to perform modal analysis of the mobile load transfer device and
on this basis
the random vibration analysis and shock response analysis are performed. The simulation result shows that the maximum deformation of the overall structure occurs at the ceramic pipes on the left and right sides
the overall stress is small and there is space for improvement in the transportation and installation scheme. On this basis
the transportation and installation modes of the device are improved. Finally
the improved scheme is analyzed and compared before and after the improvement. The result shows that the maximum deformation of the random vibration analysis after the improvement is reduced from 3.55 mm to 0.19 mm
and that of the impact response analysis is reduced from 1.43 mm to 0.52 mm and the overall stress result is small. Finally
the feasibility of the mobile load transfer device structure is verified.
Study on Seismic Performance Improvement Methods for Gas-insulated Transmission Lines (GIL) in Ultra-high Voltage Converter Station
Research on Influence of Piezoelectric Material Properties and Element Size on Sensitivity of Piezoelectric Sensor for Partial Discharge Monitoring of Transformer
Study on Temperature Distribution of Epoxy Insulated Power Electronic Transformer Based on Fluid-solid-structure Coupling
Analysis of Maximum Compression Displacement and Fatigue Life of Bellows
Related Author
YANG Rui
SI Xiaochuang
FANG Qi
XU Zhongxun
FEI Xiang
JIANG Chengbo
ZHANG Xinmiao
YUAN Duanpeng
Related Institution
Henan Pinggao Electric Co., Ltd.
Pinggao Group Co., Ltd.
CSG Extra High Voltage Power Transmission Company, Dali Bureau
China Southern Power Grid Co., Ltd.
State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University