Study on Arcing Characteristics Test of Single-phase Grounding Arc in 66 kV Petersen-coil Grounding System
为研究66 kV消弧线圈接地系统单相接地故障引起的短路电弧在空气中燃弧特性,在变电站建立了人工单相接地试验模拟平台。对消弧线圈补偿电流为92.8、97.9、103.3 A 3种工况下的接地电弧进行了试验,记录了电弧的电压、电流波形。试验结果表明:接地电弧的频率特性不随消弧线圈补偿程度而变化。起始时刻的弧道电阻与合闸角度相关,合闸角度越大,弧道电阻越大。稳定燃弧状态下,半个周波的电压变化率不随消弧线圈补偿程度而变化,为120 kV/s,而电流的变化率随消弧线圈的补偿程度而增大,分别为12、14、16 kA/s;在稳定燃弧后的不同周期内,电弧伏安曲线不一致,但其发展规律相同。稳定燃弧后的电压幅值与消弧线圈补偿程度无关,其正负幅值之差为1 200 V,消弧线圈过补偿程度越大,电流幅值越大,其幅值能够达到80 A。该研究成果可为消弧线圈的参数整定提供理论参考依据。
Abstract
In order to study the arcing characteristics of the short-circuit arc in the air due to the single-phase grounding of the 66 kV Petersen-coil grounding system
an artificial single-phase grounding test simulation platform is set up in the substation. The grounding arc is tested at conditions of Petersen-coil compensation current of 92.8 A
97.9 A and 103.3 A
and the voltage and current waveform is recorded. The test results show that the frequency characteristics of the grounding arc does not change with the compensation degree of the Petersen-coil. The arc channel resistance at the initial time is related to the closing angle
the larger the closing angle is
the greater the arc channel resistance is. Under the stable arcing state
the voltage variation rate of half cycle does not change with the compensation degree of Peterson-coil
which is 120 kV/s
while the current variation rate increases with the compensation degree of Petersen-coil
which are 12 kA/s
14 kA/s and 16 kA/s respectively. In different periods after the stable arcing
the arc volt-ampere curves are inconsistent
but its development is the same. The voltage amplitude after stable arcing has nothing to do with the compensation degree of the Petersen-coil. The difference between the positive and negative amplitudes is 1 200 V. The greater the overcompensation degree of the Petersen-coil is
the higher the current amplitude is
and its amplitude can reach 80 A. The research results can provide a theoretical reference base for the parameter setting of the Petersen-coil.
Calculation of Very Fast Transient Overvoltage with the Arc Resistance Model Considering Inductance Characteristic
Analysis on Artificial Transient Single-phase Grounding Test for 500 kV Shang- Cheng Line Ⅲ with Fixed Series Compensator
Arc Suppression Technology Based on Fast Switch for Distribution Network
Calculation and Analysis of Short Circuit Current on Two Sides of Single-phase Grounding Fault Line of Circuit-breakers Closing Transmission Line
Related Author
ZHAO Cheng-nan
OUYANG Zhuo
DUAN Shao-feng
ZHENG Ji-ling
ZHAN Hua-mao
JIA Haowei
HE Renwang
WU Wenhui
Related Institution
Beijing Area Major Laboratory of High Voltage & EMC,State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources,North China Electric Power University
East China Jiaotong University of Electrical Engineering
Electric Power Research Institute,Jibei Electric Power Company Limited
North China Electric Power Research Institute Co., Ltd.