Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
Research & Analysis|更新时间:2025-04-26
|
Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
High Voltage ApparatusVol. 61, Issue 1, Pages: 30-40(2025)
作者机构:
1.国网北京市电力公司电力科学研究院,北京 100075
2.国网北京市电力公司,北京 100032
3.国网北京市电力公司城区供电公司,北京 100034
作者简介:
基金信息:
Science and Technology Project of State Grid Beijing Electric Power Company(52022322000M)
GUI Yuan, JI Hongquan, XIN Feng, et al. Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity[J]. High voltage apparatus, 2025, 61(1): 30-40.
DOI:
GUI Yuan, JI Hongquan, XIN Feng, et al. Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity[J]. High voltage apparatus, 2025, 61(1): 30-40. DOI: 10.13296/j.1001-1609.hva.2025.01.004.
Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
For exploring the influence of temperature and humidity on the generation characteristics of characteristic components in case of partial discharge in the air
the possible components and generation in the air decomposition reaction under different temperature and humidity conditions are simulated and calculated in this paper
and a temperature and humidity controllable air partial discharge decomposition experimental platform is set up. The variation of partial discharge decomposition characteristics of air with temperature and humidity under three different typical defects is studied. The simulation and experimental results show that the main components generated by partial discharge in the air are NO
2
O
3
and CO. The contents of the three components are obviously different with variation of temperature and humidity conditions. The influence of temperature and humidity on partial discharge decomposition components under different types of defects is different. The study results can provide reference for partial discharge defect detection based on decomposition component analysis.