WANG Dongfang, NIU Bo, WANG Jing, et al. Influence of Environmental Factors on Insulation Performance of Separable Connector for 12 kV Gas Filling Switchgear Cabinet[J]. High voltage apparatus, 2025, 61(2): 10-16.
DOI:
WANG Dongfang, NIU Bo, WANG Jing, et al. Influence of Environmental Factors on Insulation Performance of Separable Connector for 12 kV Gas Filling Switchgear Cabinet[J]. High voltage apparatus, 2025, 61(2): 10-16. DOI: 10.13296/j.1001-1609.hva.2025.02.002.
Influence of Environmental Factors on Insulation Performance of Separable Connector for 12 kV Gas Filling Switchgear Cabinet
The purpose of this paper is to study the influence of environmental factors on the insulation performance of the separable connector for 12 kV gas filling cabinet and
at the same time
to provide a practical basis for the application of partial discharge discharge and chemical fusion detection in the field of insulation fault monitoring of 12 kV gas filling switchgear cabinet. The experimental model and experimental method are designed
the influence of environmental temperature and humidity on the insulation performance of the separable connector for 12 kV gas filling switchgear cabinet is studied firstly. Then
the development process of insulation fault due to high humidity
high contamination and high salinity is simulated quickly by using the method of rising the test voltage till insulation breakdown. The electrochemical sensors are used to monitor the aging products of insulation gas and study the variation of the cracking products of insulation materials after insulation breakdown. The experimental results show that high temperature
high humidity and high salinity conditions can reduce the insulation performance of the separable connector of 12 kV gas-filling switchgear cabinet
the cracking of insulation materials can produce such gases as nitric oxide
nitrogen dioxide and non-methane total hydrocarbons and
furthermore
in case of insulation fault
the worse the insulation performance of the separable connector is
the higher the concentration of the above three gases generated is
which can be used as an indicator gas for the insulation status assessment of the 12 kV gas filling switchgear cabinet.