Development and Design of 363 kV GIS with High Parameter
has a good development situation and broad market prospects. However
with the progress of science and technology
363 kV GIS from a certain company has no way to adapt to the increasingly fierce competitive environment any longer. In this paper
the circuit breaker
disconnector/earthing switch/fast earthing switch are taken as the base
the overall parameters
design and type test of the 363 kV GIS which is newly developed by our company is introduced. In the design of circuit breaker
the ablation of arc energy on arcing contact during the high current capacity test and the five-column support structure across open contacts are introduced. In the design of disconnector/earthing switch/fast earthing switch
the insulation and temperature rise ect are analyzed. And in the design of busbar
the temperature rise of conductor
the electric field and mechanical strength of the insulating spacer are analyzed. The type test shows that the newly developed 363 kV GIS meets the high parameter requirements. The rated short-circuit current of the circuit breaker is 63 kA
the standard time constant is 120 ms and the fast earthing switch meets the super class ‘B’. At present
the product has obtained full set of type tests report released by the third independent test authority and is officially applied to the substation project in the northwest region of China.