LI Hongwei, XU Xueshuai, XIONG Xiaochuan, et al. Study on Influence of Grading Capacitor on Pre-strike Characteristic of Double-break Vacuum Circuit Breaker[J]. High voltage apparatus, 2025, 61(3): 42-51.
DOI:
LI Hongwei, XU Xueshuai, XIONG Xiaochuan, et al. Study on Influence of Grading Capacitor on Pre-strike Characteristic of Double-break Vacuum Circuit Breaker[J]. High voltage apparatus, 2025, 61(3): 42-51. DOI: 10.13296/j.1001-1609.hva.2025.03.005.
Study on Influence of Grading Capacitor on Pre-strike Characteristic of Double-break Vacuum Circuit Breaker
The double-break vacuum circuit breaker can effectively improve the withstanding voltage level
significantly reduce the reignition rate
enhance the reactive power switching performance and thereby have significant practical engineering implications. In this paper
such pre-breakdown characteristic as pre-strike clearance and its dispersion
pre-strike voltage
pre-strike filed strength of double-break vacuum circuit breaker with and without shunt grading capacitors under DC voltage in case of making operation is studied through experiment
and its Weibull distribution is calculated. The result shows that the grading voltage of the double-break is more even through reasonable size of grading capacitance (about 100 pF)
thus effectively improving the pre-strike characteristic of the vacuum circuit breaker. The experimental result shows that with the increase of the grading capacitance
the pre-strike characteristic will become weak of the double-break vacuum circuit breaker when the grading capacitance exceeds 500 pF. The study in this paper can provide technical support of the double-break vacuum circuit breaker from the point of view of reducing electrical dispersion and improving controlled making accuracy.