State Grid Shanxi Electric Power Company Science and Technology Project (GIS Basin Insulator Stress Detection Based on Ultrasonic Key Technology Research and Application)
LI Xiaojing, JIAO Guoxun, YANG Cheng, et al. Research on Stress Measurement Method of GIS Insulating Spacer Based on Ultrasonic Longitudinal Wave Method[J]. High voltage apparatus, 2025, 61(3): 80-86.
DOI:
LI Xiaojing, JIAO Guoxun, YANG Cheng, et al. Research on Stress Measurement Method of GIS Insulating Spacer Based on Ultrasonic Longitudinal Wave Method[J]. High voltage apparatus, 2025, 61(3): 80-86. DOI: 10.13296/j.1001-1609.hva.2025.03.009.
Research on Stress Measurement Method of GIS Insulating Spacer Based on Ultrasonic Longitudinal Wave Method
Misalignment of conductive rod of GIS insulating spacer is one of the reasons of the insulating spacer to generate internal stress
which can cause the insulating spacer to bear partially higher stress and even generate crack
thereby resulting in such serious faults as gas leakage or partial discharge. In this paper
the stress distribution of GIS insulating spacer under the misalignment of conductive rod is analyzed. The finite element simulation software is used to simulate and calculate the stress distribution of the insulating spacer under the condition of misalignment of conductive rod. According to the simulation calculation results
the stress at different positions of the insulating spacer in case of misalignment of conductive rod is measured based on the ultrasonic longitudinal wave method and is compared with the simulation result. The result shows that the position of the maximum stress of the insulating spacer in case of misalignment of conductive rod is located in the middle position of the convex surface of the insulating spacer. Both simulation calculation and experimental measurement results are in good agreement and can be used for the stress measurement of insulating spacer.