NIU Bo, SHI Tianyi, LIU Weifeng, et al. Study on Sub-millimeter Metal Particle Initiation Characteristics in GIS Under AC Voltage Superimposed with Sinusoidal Vibration Excitation[J]. High voltage apparatus, 2025, 61(3): 96-104.
DOI:
NIU Bo, SHI Tianyi, LIU Weifeng, et al. Study on Sub-millimeter Metal Particle Initiation Characteristics in GIS Under AC Voltage Superimposed with Sinusoidal Vibration Excitation[J]. High voltage apparatus, 2025, 61(3): 96-104. DOI: 10.13296/j.1001-1609.hva.2025.03.011.
Study on Sub-millimeter Metal Particle Initiation Characteristics in GIS Under AC Voltage Superimposed with Sinusoidal Vibration Excitation
The metal particles generated in the Gas insulated metal-enclosed switchgear (GIS) is mainly the micron to sub-millimeter metal chips of such metal parts as screws and contacts due to friction and
in addition to the electric filed during the operation of the equipment
is also subjected to the sinusoidal steady excitation. To this end
the AC voltage superimposed with sinusoidal vibration excitation test platform is set up
and the initial motion and discharge characteristics of sub-millimeter metal particles of different particle sizes under the action of AC voltage alone and AC voltage superimposed with sinusoidal vibration excitation are compared and studied. The study results show that the motion of sub-millimeter metal particles at initial stage is divided into such two stages as the initial jump and the stable jump. The initial jump is characterized by the small and rapid motion of individual particle
and the jump process before entering the stable jump stage is divided into such four stages as the initial jump
the rejump
the collision-driven and the self-sustained jump. The effect of sub-millimeter metal particle size on the initial characteristics is significant
and the initial jump voltage
stable jump voltage and quenching voltage decrease and then increase with the decrease of the particle size. Compared with the condition of AC voltage
the initial jump voltage
stabilized tripping voltage and quenching voltage are decreased to some extent after the superimposed sinusoidal vibration excitation. The discharge characteristics at the initial stage are studied by the pulse current method and ultrasonic method
and the results show that sinusoidal vibration excitation can significantly reduce the PDIV
which in turn weakens the partial discharge intensity at the initial stage.