ZHANG Zongyang, KANG Chao, WANG Zhiyuan, et al. Study on Overvoltage Characteristics and Influencing Factors of UHVDC Converter Station in Grounding Fault Condition[J]. High voltage apparatus, 2025, 61(3): 144-151.
DOI:
ZHANG Zongyang, KANG Chao, WANG Zhiyuan, et al. Study on Overvoltage Characteristics and Influencing Factors of UHVDC Converter Station in Grounding Fault Condition[J]. High voltage apparatus, 2025, 61(3): 144-151. DOI: 10.13296/j.1001-1609.hva.2025.03.017.
Study on Overvoltage Characteristics and Influencing Factors of UHVDC Converter Station in Grounding Fault Condition
overvoltage will appear on some equipment in converter station. Due to different operation mode and type of equipment
it is very different from overvoltage in AC system. Based on Shanghaimiao-Linyi ±800 kV UHVDC transmission project
the overvoltage characteristics of the converter station under the conditions of DC pole line grounding
DC bus grounding and converter transformer valve side grounding fault are studied in this paper. The influence of smoothing reactor
filter capacitor and grounding pole line on overvoltage is analyzed. The study calculation provides a reference for the overvoltage suppression and insulation coordination of DC converter station with layered access at the inverter side.